Reinstalled TRH transducers in ventilation units at all levels.

Untaped pressure inlet (13:33 MST)

Started installing Licor 7500's:

...

Tried to prepare units 813 and 1163 for installation at 30 meters,
but could not get them to boot and run. Red LED at circuit board
would stay on, or blink on and off. It is supposed to go off once
the unit is running. Measured 8 V at the end of 30 meter cable
with unit attached. Need to reduce this loss.

Installed S/N 1163, and 1164 at 30 and 16 meters, but it is not cabledwitout data/power cables.Installed

Licor 7500 S/N

...

level

status

1167

43 m

port 17, working

1163

30 m

not cabled

1164

16 m

not cabled

DC power supply in power enclosure is rated at 3 A, which will not
be large enough to drive system with 5 Licor 7500s.

...

Moved network switch from adam to power enclosure. Dave Gochis will
probably use one of the ethernet ports for his Tsoil CR1000.
After this switch, the fiber/copper media converter would not
connect - even after several power cycles of converter and switch.
Had to power cycle the media converter in the seatainer. This
may mean that the fiber network will not always come up after
a power outage.

Untaped pressure inlet (13:33 MST).

Updated NIDAS software on adam.

Installed anti-climb cage on tower.