Nov 9, 12:30 MST.
Per Steve Oncley, increased the sampling rate of the Licor 7500 at 43 meters.
It is the only unit connected right now.
Commands to change the sampling rate:
# shut down data process adn # adn powers off port 17, power it back on. eio 17 1 # start minicom # The default baud rate of minicom on that port is 9600, which is what the 7500 # uses after it is sent a break. To set it to 9600 explicitly, use ctrl-A pe. # Use ctrl-A minicom commands to turn on local echo (e), line wrap (w) and send a break(f). # Set bandwidth to 10 and RS232 output frequency to 20. # Set terminator to 0A (newline): minicom ttyS17 ctrl-A pe ctrl-A e ctrl-A w ctrl-A f (Outputs (BW 10) (RS232 (Freq 20.0))) (Outputs (RS232 (EOL "0A"))) (Outputs ?) ctrl-A q # minicom should now be finished # power off port 17 eio 17 0 # start data process. This will power up port 17 aup # wait a bit, then ds ctrl-C # If the 7500 doesn't respond, try power cycling it: eio 17 0 eio 17 1