Installed the latest version of nidas (revision 5771M) today, with the new process running at 19:49 UTC.
The new nidas has some improvements in the serial handling efficiency. Don't see any effect on the number of "spurious interrupts" though.
Also restarted ntp daemon. Added a "server ral" entry in /etc/ntp.conf so that we can compare our local GPS time source with the ral server.
ntpq -p shows good agreement (-8.285 millisecond offset) with the ral server:
ntpq -p remote refid st t when poll reach delay offset jitter ============================================================================== xral 208.75.88.4 3 u 7 64 377 0.368 -8.285 1.249 oGPS_NMEA(0) .GPS. 2 l 15 16 377 0.000 -0.028 0.031
Querying the ral ntp server, with ntpq -p ral shows that it has offsets with its servers, probably related to the big delays over its wifi connection:
ntpq -p ral remote refid st t when poll reach delay offset jitter ============================================================================== +64.6.144.6 128.252.19.1 2 u 300 1024 177 43.800 -32.309 12.143 *208.75.88.4 192.12.19.20 2 u 997 1024 377 56.151 16.212 0.321 +64.73.32.134 192.5.41.41 2 u 502 1024 377 42.897 7.307 110.558
Later, Oct 16, 15:24 MDT, saw smaller offsets all around:
root@manitou root# ntpq -p remote refid st t when poll reach delay offset jitter ============================================================================== xral 208.75.88.4 3 u 39 64 377 0.354 1.108 0.390 oGPS_NMEA(0) .GPS. 2 l - 16 377 0.000 0.003 0.031 root@manitou root# ntpq -p ral remote refid st t when poll reach delay offset jitter ============================================================================== +64.6.144.6 128.252.19.1 2 u 135 1024 373 41.912 0.464 74.268 *208.75.88.4 192.12.19.20 2 u 840 1024 357 56.112 2.963 1.735 +64.73.32.134 192.36.143.150 2 u 317 1024 377 39.507 1.365 64.459
Data from the 7m TRH has been intermittent for more than a month.
Here's a typical dropout, where the unit quits reporting, then 15
hours later comes alive, with startup messages:
2010 10 02 14:07:54.4656 0 40 \x00\x00\r Sensor ID16 data rate: 1 (secs)\n 2010 10 03 05:28:49.2103 5.525e+04 29 \rcalibration coefficients:\r\n 2010 10 03 05:28:49.2517 0.04144 21 Ta0 = -4.042937E+1\r\n 2010 10 03 05:28:49.2827 0.03095 21 Ta1 = 1.022852E-2\r\n 2010 10 03 05:28:49.3134 0.0307 21 Ta2 = -2.096747E-8\r\n 2010 10 03 05:28:49.3445 0.0311 21 Ha0 = -1.479133E+0\r\n 2010 10 03 05:28:49.3773 0.03286 21 Ha1 = 3.554063E-2\r\n 2010 10 03 05:28:49.4057 0.02836 21 Ha2 = -1.382833E-6\r\n 2010 10 03 05:28:49.4390 0.03329 21 Ha3 = 3.354407E-2\r\n 2010 10 03 05:28:49.4693 0.03031 21 Ha4 = 3.666422E-5\r\n 2010 10 03 05:28:49.8050 0.3357 29 TRH16 4.91 94.96 4474 3057\r\n
Email from Ned:
the TRH at 7m now seems to be re-appearing during the night time and then at about 8am it drops out again...
http://www.eol.ucar.edu/isf/projects/BEACHON_SRM/isfs/qcdata/plots/20101001/Tprof_20101001.png
My guess is that it is a power problem, either in the cable, or corrosion in the unit. This unit and
cable was replaced on 7/22. The problem before was different, looking like a RS232 problem, where
I don't think we saw the bootup messages we're seeing now. https://wiki.ucar.edu/x/vBWdAw