Taken mostly from qctables:

Radiometers: not getting rpile.in, tcase.in, others reporting (tried pushing scan i2c button, didn't fix) → swapped in radiometer with right id for longwave in, now all reporting.

NR01: updated PIC code and plugged into uw.  Isabel updated the configuration so data are expected.

Gsoil/qsoil/lambda: plugged in with latest PIC code. Getting data from all, qsoil values are slightly negative. Is this a problem?

Tsoils: all reporting, data looks good.

Pressure: all reporting, no data in qctables because it's outside clip limits which are set for Gothic. Data looks ok in ncharts.

TRH: all reporting (just replaced fuse + housing for 13m trh, it's reporting now but not yet making it to qctables), data looks good.

CSAT: all reporting after I swapped the sonic head on 10m.c (and previous resetting of some EC100's using ECmon).  Some heads are intermittent, but I presume this will clear up in the field.

EC150:

  • all h2o reporting.  Some heads were blocked by foam padding. 
  • alll co2 reporting, but about half are clipped.  Hoping this will go away in the field.
  • Note that, in the ECmon reconfiguring, I noticed 2 EC100 boxes that were set to force Tirga to 25C.  I think these are all fixed now.

Pillows: working, needed reboot of cl

Flowcaps: getting data from both flowcaps.  The second needed to have the power switch turned on its USB adaptor.  Both are now configured to the averaging we want (30/30/300).

Apogee IR: all reporting. Raw values look good, Steve is working on debugging the surface temp calculation.

Tsnows: Currently plugged in to d and ue.  (uw is done, but Chris is protecting the sensors so the cable doesn't reach.)  Looks good. 

Gps/chrony: finally started getting good GPS on uw, but just recently stopped getting good gps on ct. I'll look into it, see jira for more details. → ct fixed itself after I pulled the GPS antenna out to rest on the top of the dsm box.

Victrons: not staged, not planning to stage (actually want to stage at least one as part of a power drop test – Tony is building up power boxes for this)

Anything else I'm forgetting??