Just a scratch space for us to use for burn-in. Granted, it is still early for this, as things are being installed, but I did want to note one item:
Adding what I can see from logging directly into dsms (there are some problems I'm still looking into that show more data being missing on qctables...)
- tt: 7m csat3a/ec150 (ttb port 0) not reporting (wasn't plugged in)
- tt: 28m csat3a/ec150 (ttt port 0) all nans for co2/h2o (wasn't plugged in)
- t0: 2m TRH (t0b port 4) not reporting (bad port 4, moved to t0t port 7)
- t0: 3m TRH (t0t port 1) reports all zeros, far less than once a second
- t2: 4m TRH (port 3) not reporting
- t2: 4m csat3a/ec150 (port 2) not reporting
- t7: 4m csat3 (port 0) ldiag always nonzero
- t8: issues with dsm serial card (this may be the reason for all the t7/8/9 sensor problems) (dsm replaced, seems fine)
- t8: 4m csat3a/ec150 (port 2) not reporting (bad dsm)
- t8: 4m TRH (port 3) not reporting (bad dsm)
- t8: 4m nano (port 4) reporting init string only (bad dsm)
- t9: 4m csat3a (port 5) reporting in ascii mode, not being parsed (taken back to site to configure)
- t10: 4m csat3 (port 0) not reporting (tried other ports, probably not a port problem)
- t15: 4m csat3a (port 5) not reporting (wasn't installed)
- t17: 4m TRH (port 3) not reporting (it was earlier) (restarted dsm)
- t17: 4m nano (port 4) not reporting (it was yesterday) (restarted dsm)
- t18: 4m csat3b (port 5) not reporting (it was yesterday) (restarted dsm)
- t19: 4m csat3 (port 0) not reporting (box wasn't installed)
- t20: 4m TRH (port 3) bad rfan (replaced housing)
- t21: 4m csat3a (port 5) not reporting (needs data cable)
- t22: 4m csat3 (port 0) not reporting (box wasn't installed)
- t23: soils not reporting (rescanned mote)
- t23: 4m TRH (port 3) not reporting (added fuse to port 3)
- t24: 4m csat3b (port 5) not reporting (wasn't installed)
- t25: 4m csat3 (port 0) not reporting (box wasn't installed)
- t26: 4m csat3a/ec150 (port 2) not reporting (plugged in power inside box)
- t26: 4m csat3a/ec150 (port 2) set in ascii mode, taking box back to base
- t27: 4m csat3a (port 5) not reporting (added data cable)
- t28: 4m csat3 (port 0) not reporting (box wasn't installed)
- t29: TRH T is low. RH is fine. Maybe just needs to have new cal re-uploaded?
- t30: 4m csat3b (port 5) not reporting (wasn't installed)
- t31: 4m csat3 (port 0) not reporting (box wasn't installed)
- t33: 4m csat3b (port 5) not reporting (updated sonic type in config)
- t34: 4m csat3 (port 0) not reporting (box wasn't installed)
- t36: 4m csat3b (port 5) not reporting (wasn't installed)
- t37: 4m csat3 (port 0) not reporting (box wasn't installed)
- t39: 4m csat3 (port 5) not reporting (box wasn't installed)
- t40: 4m csat3 (port 0) not reporting (box wasn't installed)
- t42: 4m csat3b (port 5) not reporting (wasn't installed)
- t43: 4m csat3 (port 0) not reporting (box wasn't installed)
- t45: 4m csat3 (port 5) not reporting (box wasn't installed)
- t46: 4m csat3 (port 0) not reporting (box wasn't installed)
- t47: 4m nano (port 5) not reporting, most likely ec100 box wiring issue? taking box back to base
- t48: 4m csat3b (port 5) not reporting (wasn't installed)
- t49: 4m csat3 (port 6) not reporting (box wasn't installed)
- t49: tsoil not reporting (rest of mote sensors are fine) (replaced)
1 Comment
Steve Oncley AUTHOR